TCB50 & TCB110: Conversion module compatible with all standard mains ballasts. TCB modules require an un-switched 230 volt supply to monitor the local sub-circuit. These units may be connected to 50 or 110 volt maintained or non-maintained AC/DC central battery units and will operate any standard fluorescent lamp in the range 4-70 Watts.
HCB50 & HCB110: Slave inverter module requiring an un-switched 230volt supply to monitor the local sub-circuit. These units may be connected to 50 or 110 volt maintained AC/DC central battery units and will operate any standard fluorescent lamp in the range 4-70 Watts.
CCB50 & CCB110: Slave inverter module for connection to 50 or 110 volt non-maintained AC/DC central battery units (or for continuous operation from a maintained AC/DC system). These inverters will operate any standard fluorescent lamp in the range 4-70 Watts.