Menu
ELP Track EM - self-contained track mounted LED downlight

Track EM – Self-Contained Track Mounted LED Downlight

The Track EM unit offers a simple method of providing discreet emergency lighting in areas that require a self-contained solution powered by the existing track system (Eutrac or Global Track).

Supplied with a ‘clip-in’ symmetrical wide angle lens or asymmetrical ‘corridor’ lens for escape routes (both supplied) the Track EM luminaire simply connects to a permanent 230 volt supply via the integral track adaptor to provide effective emergency lighting with 3 hour duration.

Standard Self-Test
Incorporating tried and tested emergency driver technology from the ELP proSeries, the Track EM offers self-contained, non-maintained emergency lighting with integral automatic Self-Test.

Optional DALI
Utilising appropriate Eutrac or Global Track with DALI conductors and a DALI test system (such as the ELP SurePath system) the Track EM/DALI option can provide central DALI testing. Switchable maintained operation is possible by using the DALI system to switch the LED on or off in mains healthy conditions.

DALI and Self-Test logos

Datasheet (PDF)
Register to download additional product data including LDT Files, Wiring Diagrams and Certificates of ConformityCLICK HERE

 

Category: Tags: ,

Description

The Track EM can be specified for use with Eutrac or Global track systems (standard or DALI). The enclosure houses an ‘intelligent’ proSeries LED driver/ battery charger and a Lithium Iron Phosphate (LiFe) battery. The integral downlight utilises a Nichia ‘3Watt’ high power white LED operating in conjunction with a wide angle or ‘corridor’ distribution lens. The Lithium Iron battery technology ensures long life without the thermal concerns associated with the more common Nickel Metal Hydride battery technology.

The Track EM steel housing is available finished in white (white downlight body) or black (silver downlight body).

The Track EM luminaire is mechanically locked onto the track.

DALI and Self-Test logos

Operation Table

OperationSubjectPlastic housing
EnvironmentalProtection against electric shockClass I
Ingress protectionIP20
Rated operating ambient temperature0 to 35°C
MountingEutrac or Global Track (mechanically locked)
Mains operationRated voltage supply220/240V AC
Mains frequency50/60Hz
Mains supply current20mA
Emergency operationEmergency duration3 hours
Battery recharge period<24 hours
Battery chargingIntelligent constant voltage
Battery discharge current - nominal375mA
Lumen output190 lumens (max)
Integral test routineEN62034/DALI
MechanicalDimensions (surface)50.4mm (H) x 415.0mm (L) x 58.0mm (D)
Electrical connectionIntegral Eutrac or Global adaptor
Mains inputHook and spring catch

Spacing Table

 
Track EM/C
Track EM/105
Mounting height
Hm (m)
Spacing (m)
min 0.5Lux
open area
Spacing (m)
min 1Lux
escape
Spacing (m)
min 0.5Lux
open area
Spacing (m)
min 1Lux
escape
2.0
n/a
10.0
7.9
6.8
2.5
n/a
11.0
8.8
7.9
3.0
n/a
12.0
9.4
9.1

Order Codes

Order CodesDescription
STANDARD (non-DALI) versions
TR/NM3/ST/9005/GSelf-Test, non-maintained, black with Global track adaptor
TR/NM3/ST/9005/ESelf-Test, non-maintained, black with EUTRAC track adaptor
TR/NM3/ST/9010/GSelf-Test, non-maintained, white with Global track adaptor
TR/NM3/ST/9010/ESelf-Test, non-maintained, white with EUTRAC track adaptor
DALI versions
TR/M3/ST/9005/GDALI, maintained, black with Global track adaptor (switching of the mains operation via DALI)
TR/M3/ST/9005/EDALI, maintained, black with EUTRAC track adaptor (switching of the mains operation via DALI)
TR/M3/ST/9010/GDALI, maintained, white with Global track adaptor (switching of the mains operation via DALI)
TR/M3/ST/9010/EDALI, maintained, white with EUTRAC track adaptor (switching of the mains operation via DALI)